Power Triangle Calculator

Table of Contents

Every AC load has three kinds of power: real power (kW) that does the work, reactive power (kVAR) that sustains magnetic and electric fields, and apparent power (kVA) that the system has to carry. This free power triangle calculator solves all three, plus the power factor and its angle, from any two values you know. The triangle is drawn to scale, a gauge shows where your power factor sits, and a what-if slider shows how much kVAR it would take to reach your target.

Power Triangle Calculator

Enter any two of real power (P), reactive power (Q), apparent power (S) and power factor to solve the whole power triangle. Includes an animated triangle drawn to scale, a power factor gauge and a what-if slider that shows how much kVAR it takes to reach your target.

S² = P² + Q²  |  pf = cos θ = P / S  |  Q = P · tan θ
Try an example
I know:
Power factor:
Known values
Enter the size of Q. The lagging or leading choice sets its sign.
Switch the format to enter the power factor angle instead.
Output units and target power factor
Used for the kVAR-to-target result and the what-if slider.
Link copied. It opens this calculator with your inputs filled in.
Power factor
—
Real power P
—kW
Reactive power Q
—kVAR
Apparent power S
—kVA
Power factor angle θ
—°
Reactive factor sin θ
—
tan θ = Q / P
—
kVAR to reach 0.95
—kVAR
S at 0.95
—kVA
The power triangle (to scale)
Power factor gauge
Show step-by-step solution
    Standard formulas (consistent with IEEE Std 141, the IEEE Red Book) S = √(P² + Q²), pf = cos θ = P / S, Q = S · sin θ = P · tan θ, θ = arctan(Q / P). Lagging (inductive) loads absorb reactive power (+Q). Leading (capacitive) loads supply it (−Q).
    Reactive power to raise the power factor from pf₁ to pf₂ at the same real power: Qc = P · (tan θ₁ − tan θ₂). For capacitor bank sizing, voltage rating and NEC checks, use the Power Factor Correction Calculator.
    NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association. ShaiLearning is not affiliated with or endorsed by NFPA.
    IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc. ShaiLearning is not affiliated with or endorsed by IEEE. IEEE standards are available from IEEE.
    Results are for educational and preliminary reference only. Always verify against applicable project standards, AHJ requirements, and licensed engineering judgment.
    See more resources: FE and PE Electrical Guide

    How to Use the Power Triangle Calculator

    1. Pick the two values you know: P & pf, S & pf, Q & pf, P & Q, P & S, or Q & S.
    2. Choose lagging or leading. Inductive loads such as motors and transformers lag and absorb reactive power (+Q). Capacitive loads lead and supply it (−Q).
    3. Enter the values in W, kW or MW (and the matching VAR and VA units). You can enter power factor as a decimal, a percent or an angle in degrees.
    4. Set a target power factor (optional). The default is 0.95. Open Output units and target power factor to change it or to switch the result units.
    5. Solve. You get P, Q, S, pf, θ, sin θ and tan θ, plus the kVAR needed to reach your target. Drag the what-if slider to see the triangle shrink or grow, and open Show step-by-step solution for every substitution.

    Power Triangle Formulas

    • Apparent power: S = √(P² + Q²)
    • Power factor: pf = cos θ = P / S
    • Reactive power: Q = S × sin θ = P × tan θ
    • Power factor angle: θ = arctan(Q / P) = arccos(pf)
    • Reactive power to correct from pf₁ to pf₂: Qc = P × (tan θ₁ − tan θ₂)

    The triangle works the same for single-phase and three-phase systems. For three-phase loads, use total three-phase P, Q and S.

    Worked Examples

    100 kW at 0.80 pf lagging

    1. θ = arccos(0.80) = 36.87°
    2. S = 100 / 0.80 = 125 kVA
    3. Q = 125 × sin 36.87° = 75 kVAR, the classic 3-4-5 triangle
    4. To reach 0.95: Qc = 100 × (0.750 − 0.329) = 42.1 kVAR, which cuts S to 105.3 kVA

    75 kW on a 100 kVA load

    Q = √(100² − 75²) = 66.1 kVAR and pf = 75 / 100 = 0.75.

    FE/PE Exam and Field Tips

    • Keep track of the sign of Q. Lagging is +Q and leading is −Q. Adding capacitors subtracts kVAR from a lagging load.
    • Correction keeps P constant. Capacitors don’t change real power. They shrink Q, so S and current drop.
    • Diminishing returns. Going from 0.80 to 0.95 cuts S by about 16%. Going from 0.95 to 1.0 takes another 32.9 kVAR per 100 kW but cuts S by only 5%.
    • Need current too? Convert kW or kVA to amps with the kW to Amps Calculator .
    • Sizing a capacitor bank? Use the Power Factor Correction Calculator for the kVAR, capacitor current and NEC Article 460 checks.
    FAQ

    Frequently Asked Questions

    What is the power triangle?

    It is a right triangle that shows how real power P (the horizontal side), reactive power Q (the vertical side) and apparent power S (the hypotenuse) relate. The angle θ between P and S is the power factor angle, and cos θ is the power factor.

    How do I calculate kVA from kW and power factor?

    Divide kW by the power factor: S = P / pf. For example, 80 kW at 0.8 pf is 100 kVA.

    How do I find kVAR from kW and kVA?

    Use the Pythagorean relationship: Q = √(S² − P²). For example, a 100 kVA load drawing 80 kW has Q = √(100² − 80²) = 60 kVAR.

    What is the difference between lagging and leading power factor?

    With a lagging power factor, the current lags the voltage and the load absorbs reactive power. Induction motors, transformers and other inductive loads behave this way. With a leading power factor, the current leads the voltage and the load supplies reactive power, as capacitor banks and lightly loaded cables do.

    What is a good power factor?

    Many facilities aim for 0.95 or higher, and many utilities apply charges below a threshold, often somewhere between 0.85 and 0.95 depending on the tariff. Check your utility's rate schedule for the exact limit.

    How many kVAR do I need to improve power factor?

    Qc = P × (tan θ₁ − tan θ₂), where θ₁ and θ₂ are the angles for the present and target power factors. The calculator shows this for your target, and the what-if slider lets you try others.

    Does the power triangle apply to three-phase systems?

    Yes. Use the total three-phase P, Q and S and the same relationships hold. For balanced loads, each phase carries one third of each.

    Related Calculators

    Preparing for the FE or PE Electrical Exam?

    Get structured guidance from a licensed P.E. through the ShaiLearning FE & PE mentorship program. Join the waitlist, and explore the FE Electrical Guide and PE Power Guide.

    NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association. ShaiLearning is not affiliated with or endorsed by NFPA.

    Results are for educational and preliminary reference only. Always verify against applicable project standards, AHJ requirements, and licensed engineering judgment.

    Leave a Reply

    Your email address will not be published. Required fields are marked *

    Related posts you might like

    Impedance Calculator

    This impedance calculator finds Z in rectangular and polar form from R and X, from |Z| and angle, from series

    Read More »

    Ohm’s Law Calculator

    The Ohm’s law calculator solves for voltage, current, resistance, and power from any two known values. Ohm’s law is the

    Read More »

    Why Large Power is Transmitted at High-Voltage

    Electricity is rarely made where it is used. A high voltage transmission system makes it possible to reach all demand

    Read More »