kW to amps calculator

Table of Contents

How many amps does a 100 kW load draw at 480 V? What current will a 500 kVA transformer carry at 208 V? This free kW to amps calculator answers those questions for three-phase, single-phase and DC circuits. It works from kW, kVA or horsepower, and also converts amps back to kW and kVA. It shows how the same load’s current changes across common voltages and power factors, with every step of the math.

kW to Amps Calculator

Convert kW, kVA or horsepower to amps, or amps back to kW and kVA, for three-phase, single-phase and DC circuits. See how current changes with voltage and power factor, with every step shown.

3φ: I = P / (√3 · VLL · pf)  |  1φ: I = P / (V · pf)  |  DC: I = P / V
Try an example
Convert:
System:
Voltage given:
I know:
Inputs
Shaft output. Input power = HP × 0.746 / η.
Line current.
Use 1.0 for resistive loads such as heaters.
Voltage adjustment (optional)
For example, 95 to check current at a 5% low voltage. Constant-power loads draw more current when voltage drops.
Link copied. It opens this calculator with your inputs filled in.
Line current
—
Current
—A
Real power P
—kW
Apparent power S
—kVA
Reactive power Q
—kVAR
Voltage used
—V
Amps per kW
—A/kW
Current at common voltages
Current vs power factor
Quick reference at common voltages
Show step-by-step solution
    Standard formulas (consistent with IEEE Std 141, the IEEE Red Book) Three-phase with line-to-line voltage: I = P / (√3 · VLL · pf) = S / (√3 · VLL). With line-to-neutral voltage: I = P / (3 · VLN · pf). Single-phase: I = P / (V · pf) = S / V. DC: I = P / V. Motors: Pin = HP × 0.746 kW / η.
    Reverse: S = √3 · VLL · I (3φ) or V · I (1φ), P = S · pf, Q = S · sin(arccos pf).
    Calculated motor current is an estimate. For NEC conductor and protection sizing, use the full-load current tables of Article 430 (see the Motor Full-Load Current Calculator).
    NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association. ShaiLearning is not affiliated with or endorsed by NFPA.
    IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc. ShaiLearning is not affiliated with or endorsed by IEEE. IEEE standards are available from IEEE.
    Results are for educational and preliminary reference only. Always verify against applicable project standards, AHJ requirements, and licensed engineering judgment.
    See more resources: FE and PE Electrical Guide

    How to Use the kW to Amps Calculator

    1. Choose the direction. Power → Amps finds current. Amps → Power finds kW, kVA and kVAR from a measured or rated current.
    2. Choose the system. Pick three-phase, single-phase or DC. For three-phase, say whether your voltage is line-to-line (for example, 480 V) or line-to-neutral (for example, 277 V).
    3. Enter what you know. Real power in kW, apparent power in kVA, or motor horsepower with efficiency. Switch units between W, kW and MW, or V and kV.
    4. Enter the power factor for AC loads. Use 1.0 for resistive loads such as heaters. A kVA input doesn’t need one.
    5. Calculate. You get the current (switch the result between A, kA and mA), plus kW, kVA, kVAR and amps per kW. The charts and quick-reference table show the same load at common voltages and power factors.

    kW to Amps Formulas

    • Three-phase: I = P × 1000 / (√3 × VLL × pf), or I = P × 1000 / (3 × VLN × pf)
    • Single-phase: I = P × 1000 / (V × pf)
    • DC: I = P × 1000 / V
    • kVA to amps: I = S × 1000 / (√3 × VLL) for three-phase, or S × 1000 / V for single-phase
    • Horsepower: input kW = HP × 0.746 / η, then apply the kW formula
    • Amps to kW: P = √3 × VLL × I × pf / 1000 (three-phase) or V × I × pf / 1000 (single-phase)

    P is in kW, S in kVA, V in volts and I in amps. The √3 comes from the relationship between line-to-line and line-to-neutral voltage in a balanced three-phase system.

    Worked Examples

    100 kW at 480 V three-phase, 0.85 pf

    I = 100,000 / (1.732 × 480 × 0.85) = 141.5 A. At unity power factor the same 100 kW would draw only 120.3 A, 15% less.

    500 kVA transformer at 208 V three-phase

    I = 500,000 / (1.732 × 208) = 1,388 A. Power factor doesn’t matter here because the rating is in kVA.

    7.2 kW heater at 240 V single-phase

    I = 7,200 / 240 = 30 A, with pf = 1.0 for a resistive load.

    FE/PE Exam and Field Tips

    • Check which voltage you have. 480 V is line-to-line, and 277 V is the matching line-to-neutral value. Using √3 with a line-to-neutral voltage is a common error.
    • kW needs power factor and kVA doesn’t. That’s why equipment that serves any load, such as transformers and generators, is rated in kVA.
    • Higher voltage, lower current. Current scales with 1/V. The same load draws 2.3 times more current at 208 V than at 480 V.
    • Calculated motor current isn’t NEC current. For motor wire and breaker sizing, use the table values in the Motor Full-Load Current Calculator .
    • Constant power vs. constant impedance. At low voltage a motor draws more current, but a heater draws less. The voltage adjustment option assumes constant power.
    FAQ

    Frequently Asked Questions

    How do I convert kW to amps for a three-phase load?

    Divide the power in watts by √3 × line-to-line voltage × power factor: I = P / (√3 × V × pf). For example, 50 kW at 480 V and 0.9 pf is 50,000 / (1.732 × 480 × 0.9) = 66.8 A.

    How many amps is 1 kW?

    It depends on voltage, phase and power factor. At unity power factor, 1 kW draws about 8.33 A at 120 V single-phase, 4.17 A at 240 V single-phase, 2.78 A at 208 V three-phase and 1.20 A at 480 V three-phase.

    What is the difference between converting kW and kVA to amps?

    kVA is apparent power, so current follows directly from voltage: I = S / (√3 × V) for three-phase. kW is real power, so you also need the power factor: I = P / (√3 × V × pf). For the same kW, a lower power factor means more current.

    Should I use line-to-line or line-to-neutral voltage?

    Either works if you use the matching formula. With line-to-line voltage use √3 × VLL, and with line-to-neutral voltage use 3 × VLN. The calculator lets you choose, and it converts the voltage you entered when you switch.

    Can I convert horsepower to amps?

    Yes. Choose Horsepower, enter the efficiency and power factor, and the calculator finds input kW = HP × 0.746 / η, then the current. This is an estimate. For NEC conductor and protection sizing, use Article 430's full-load current tables instead.

    How do I convert amps to kW?

    Switch to Amps → Power. For three-phase, P = √3 × V × I × pf / 1000. For single-phase, P = V × I × pf / 1000. For DC, P = V × I / 1000.

    Is this current the same as the wire ampacity I need?

    No. This is the load current. Conductor sizing adds code factors, such as 125% for continuous loads, plus temperature and bundling corrections and voltage drop. Use the Voltage Drop & Wire Size Calculator for that step.

    Related Calculators

    Preparing for the FE or PE Electrical Exam?

    Get structured guidance from a licensed P.E. through the ShaiLearning FE & PE mentorship program. Join the waitlist, and explore the FE Electrical Guide and PE Power Guide.

    NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association. ShaiLearning is not affiliated with or endorsed by NFPA.

    Results are for educational and preliminary reference only. Always verify against applicable project standards, AHJ requirements, and licensed engineering judgment.

    Leave a Reply

    Your email address will not be published. Required fields are marked *

    Related posts you might like

    Impedance Calculator

    This impedance calculator finds Z in rectangular and polar form from R and X, from |Z| and angle, from series

    Read More »

    Ohm’s Law Calculator

    The Ohm’s law calculator solves for voltage, current, resistance, and power from any two known values. Ohm’s law is the

    Read More »

    Why Large Power is Transmitted at High-Voltage

    Electricity is rarely made where it is used. A high voltage transmission system makes it possible to reach all demand

    Read More »