Three-Phase & Single-Phase Power Calculator

Table of Contents

We built this three-phase power calculator to solve balanced, unbalanced, and single-phase loads. After all, whether you’re checking a 480 V motor feeder, a 240 V air conditioner, or a PE exam problem, power calculations come down to the same few relationships between voltage, current, power factor, and kW. In addition, it gives you kW, kVA, kVAR, current, voltage, phase values, and per-unit values from any combination you know, and then shows every step. You can start by selecting any of the try examples.

Three-Phase & Single-Phase Power Calculator

kW, kVA, kVAR, current and voltage for balanced or unbalanced three-phase and single-phase loads, with phasors, waveforms, per-unit values and step-by-step solutions.

S = √3·VLL·IL  |  P = S·cos φ  |  Q = S·sin φ
Try an example
System:
Load:
I know:
Enter loads as:
Connection:
Phase sequence:
pf type:
Frequency:
Inputs
Phase A (A–N)
Phase B (B–N)
Phase C (C–N)

Per-unit values (optional)
Three-phase base.
Line-to-line base. Leave blank to use the system voltage.
For change of base, transformer %Z and multi-zone systems, see the Per-Unit System Calculator.
Link copied. It opens this calculator with your inputs filled in.
Apparent power S
—
Real power P
—
Reactive power Q
—
Line current IL
—
Line voltage VLL
—
Power factor · angle φ
—
Overall power factor
—
Neutral current IN
—
Line current unbalance
—%
Per phase (Wye)
Phase voltage Vph
—
Phase current Iph
—
Power per phase
—
Load impedance Zph
—Ω
Zph = R + jX
—Ω
Equivalent L per phase
—
Per-unit
Zbase
—Ω
Ibase
—
Load Z (per unit)
—pu
S (per unit)
—pu
V (per unit)
—pu
I (per unit)
—pu
Power triangle (to scale)Live
Phasor angles (VAN = 0° reference)
Rotating phasors & waveforms Slowed to 1 cycle every 4 s
Diagram rotation:
Line-to-line phasors:
Instantaneous power over one cycle
Show step-by-step solution
    Standard formulas (consistent with IEEE Std 141, the IEEE Red Book) Three-phase (balanced): S = √3·VLL·IL  |  P = S·cos φ  |  Q = S·sin φ  |  Wye: Vph = VLL/√3, Iph = IL  |  Delta: Vph = VLL, Iph = IL/√3
    Single-phase: S = V·I  |  P = V·I·cos φ  |  Q = V·I·sin φ  |  Z = V/I. V is the voltage across the load: line-to-neutral (e.g., 120, 230, 277 V) or line-to-line (e.g., 208, 240, 480 V).
    Unbalanced: each phase is solved with phasors, Sk = Vk·Ik*. 4-wire wye: IN = IA + IB + IC. Delta: IA = IAB − ICA, and so on. Total S = √(ΣP² + ΣQ²) (vector sum). Assumes an ideal balanced source. An ungrounded 3-wire wye with unbalanced load (neutral shift) is not covered.
    Sequence ABC: VAB = √3·VAN∠+30°. CBA (ACB): ∠−30°. Per-unit: Zbase = kVbase²/MVAbase. 3φ: Ibase = MVA/(√3·kV), using line-to-line kV, three-phase MVA and the equivalent wye impedance. 1φ: Ibase = MVA/kV.
    Instantaneous power of each load element: p(t) = V·I·[cos(θv − θi) − cos(2ωt + θv + θi)]. A balanced three-phase total is constant. Phasors rotate counterclockwise by convention; the clockwise option only mirrors the diagram. Current unbalance = maximum deviation from the average ÷ average.
    IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc. ShaiLearning is not affiliated with or endorsed by IEEE. IEEE standards are available from IEEE.
    Results are for educational and preliminary reference only. Always verify against applicable project standards, AHJ requirements, and licensed engineering judgment.
    See more resources: FE and PE Electrical Guide
    —

    How to Use the Three-Phase Power Calculator

    1. First, choose the system. Pick Three-Phase or Single-Phase. For three-phase, also choose a balanced or unbalanced load, Wye or Delta, and the phase sequence (ABC or ACB).
    2. Next, pick what you know. For example, enter V, I and pf; V, P and pf; V, S and pf; or P, I and pf. The calculator then solves for everything else. For unbalanced loads, however, enter each phase as kW + pf or as R + jX.
    3. Then choose units. Enter values in V or kV and A or kA, as well as kW or MW. Also, each result has its own unit dropdown, so you can view S in kVA or MVA without recalculating.
    4. Also, add per-unit bases (optional) to get Zbase, Ibase and the load in per-unit.
    5. Finally, click Calculate, and then explore the rotating phasors, the instantaneous power plot and the power triangle. Afterward, open Show step-by-step solution to see every substitution, or use Print / Save as PDF for a one-page report.

    Three-Phase and Single-Phase Power Formulas

    Because a balanced three-phase system has three equal voltages 120° apart, its total power is three times the power in one phase. As a result, the formulas below work with either line or phase values, as long as you pair them correctly.

    • Three-phase apparent power: S = √3 × VLL × IL
    • Single-phase apparent power: S = V × I (no √3)
    • Real and reactive power: P = S × cos φ and Q = S × sin φ, where cos φ is the power factor
    • Wye: Vph = VLL/√3 and Iph = IL. Delta: Vph = VLL and Iph = IL/√3
    • Per-phase impedance: Z = Vph/Iph, with R = Z cos φ and X = Z sin φ
    • Unbalanced 4-wire wye: IN = IA + IB + IC (phasor sum)

    The √3 appears because line-to-line voltage in a balanced three-phase system is √3 times the phase voltage. In general, the calculator follows the methods in IEEE Std 141 (Red Book). Also, for the SI basis of watts, volts and amperes (1 V = 1 W/A), see the NIST SI units page for electric current.

    Three-Phase Power Calculator Examples

    Example 1: Three-phase power at 480 V, 100 A, 0.85 pf

    Three-phase power calculator results for 480 V, 100 A at 0.85 pf: 83.14 kVA and 70.67 kW, with rotating phasors, instantaneous power and the power triangle
    The three-phase power calculator solving the 480 V, 100 A example.
    1. First, S = √3 × 480 × 100 = 83.14 kVA
    2. Then P = 83.14 × 0.85 = 70.67 kW
    3. Next, φ = arccos(0.85) = 31.79°, so Q = 83.14 × sin 31.79° = 43.80 kVAR
    4. Finally, for a wye load, each phase sees 480/√3 = 277.1 V and carries 100 A, so Z = 2.771 Ω ∠31.79° (2.356 + j1.460 Ω).

    Also, as a check, P² + Q² = S², so 70.67² + 43.80² ≈ 83.14².

    Example 2: Single-phase power at 240 V, 30 A, 0.9 pf

    In this case, S = 240 × 30 = 7.20 kVA, P = 7.20 × 0.9 = 6.48 kW, and Q = 3.14 kVAR. Notice there is no √3, so using it here is a common mistake.

    Example 3: Unbalanced three-phase power, 10, 6 and 3 kW on a 208Y/120 V system

    In this case, with phases A, B and C at 0.9, 0.8 and 1.0 pf, the line currents are 92.5 A, 62.5 A and 25.0 A. Because they are not equal or 120° apart, the neutral carries 45.2 A. In contrast, a balanced load would put zero current on the neutral.

    In practice, then, spreading single-phase loads evenly across the phases keeps the neutral current low. As a result, it also reduces neutral heating.

    Three-Phase Power Tips for the FE/PE Exam and the Field

    • First, match the voltage to the formula. √3 goes with line-to-line voltage. However, if a problem gives phase voltage, use P = 3 × Vph × Iph × pf instead.
    • The connection changes phase values, not total power. For example, a delta load at the same line voltage and current draws the same kW as a wye load.
    • Watch the phase sequence. For instance, with ABC sequence, VAB leads VAN by 30°. In contrast, with CBA, it lags. Also, swapping two phases reverses a motor's rotation.
    • Three-phase power is smooth. Single-phase power pulses at twice line frequency, while a balanced three-phase total is constant. The calculator's instantaneous power plot therefore shows why three-phase motors run smoothly.
    • Low power factor? Then size capacitors with the Power Factor Correction Calculator.
    FAQ

    Frequently Asked Questions

    What can this three-phase power calculator solve?

    In short, it finds kW, kVA, kVAR, current, voltage, phase values and per-unit values for balanced, unbalanced and single-phase loads. In addition, it shows the neutral current for unbalanced wye loads, and then lists every step.

    What is the difference between single-phase and three-phase power formulas?

    In short, single-phase uses S = V × I. In contrast, three-phase uses S = √3 × VLL × IL with line-to-line voltage, or 3 × Vph × Iph with phase values. However, both use P = S × pf and Q = S × sin φ.

    How do I convert kW to amps for a three-phase load?

    In general, I = P / (√3 × VLL × pf). For example, 50 kW at 480 V and 0.86 pf draws 50,000 / (1.732 × 480 × 0.86) ≈ 69.9 A. Also, choose "V, P, pf" in the calculator to do this automatically.

    What voltage should I use for a single-phase load?

    Basically, use the voltage across the load. For example, that's line-to-neutral for 120 V or 277 V loads, and line-to-line for 208 V, 240 V or 480 V loads.

    Related Calculators

    Next, try these related tools, since each one builds on the same ideas.

    Preparing for the FE or PE Electrical Exam?

    Get structured guidance from a licensed P.E. through the ShaiLearning FE & PE mentorship program. Join the waitlist, and explore the FE Electrical Guide and PE Power Guide.

    IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc. ShaiLearning is not affiliated with or endorsed by IEEE. IEEE standards are available from IEEE.

    Results are for educational and preliminary reference only. Always verify against applicable project standards, AHJ requirements, and licensed engineering judgment.

    Leave a Reply

    Your email address will not be published. Required fields are marked *

    Related posts you might like

    Transformer Sizing Calculator

    This transformer sizing calculator recommends a standard transformer rating from your plant output or load list. Picking a transformer rating

    Read More »

    Power Factor Correction Calculator

    The power factor correction calculator sizes the capacitor bank you need and shows what the correction buys you. Low power

    Read More »

    Impedance Calculator

    This impedance calculator finds Z in rectangular and polar form from R and X, from |Z| and angle, from series

    Read More »