Voltage Drop and Wire Size Calculator

Table of Contents

A conductor can carry its load without overheating and still deliver too little voltage at the far end. Long feeders, low-voltage DC runs and motor circuits are where this bites. This free voltage drop calculator finds the smallest copper or aluminum conductor that meets both ampacity and your voltage drop limit. It uses NEC 2023 Table 310.16 and the Chapter 9 resistance and reactance tables, and handles ambient correction, conductor bundling, continuous loads and parallel sets. You also get an animated cable run, a drop-versus-length graph and a phasor diagram, plus every step of the math.

Voltage Drop & Wire Size Calculator

Find the smallest conductor that meets both ampacity and voltage drop, using NEC 2023 Table 310.16 and Chapter 9 Tables 8 & 9, with correction factors, parallel sets and an animated cable run.

VD = k · I · L · (R cos θ + X sin θ)  |  k = √3 (3φ), 2 (1φ, DC)
Try an example
System:
I know:
Impedance model:
Conductor:
Conduit:
Table 8 options:
Circuit
Used for X sin θ in the AC model. Table 9's printed Ze assumes 0.85.
NEC informational notes suggest about 3% (branch circuit or feeder) and 5% total.
More than 1 set: 1/0 AWG and larger only (310.10(G)).
Ampacity conditions (Table 310.16, 310.15 and 110.14(C))
Insulation rating:
Terminal rating:
Continuous load:
Table 310.15(B)(1)(1). Rooftop raceways may need the 310.15(B)(2) adder.
More than 3 applies Table 310.15(C)(1). Count every conductor of each parallel set in the same raceway.
Link copied. It opens this calculator with your inputs filled in.
Recommended conductor
—
Voltage drop
—%
Voltage drop
—V
Voltage at load
—V
Load current
—A
Allowable ampacity
—A
Max length at limit
—ft
Conductor losses
—kW
Aluminum option
—
The cable runDots show current flow
Voltage drop vs length
Voltage drop phasors (per phase)
Nearby sizes (your conditions)
Show step-by-step solution
    Method per NFPA 70® (NEC®) 2023, consistent with IEEE Std 141 (Red Book) AC model: VD = k · I · L · Ze / n, where Ze = R cos θ + X sin θ (Chapter 9 Table 9, Note 2), k = √3 for three-phase (line-to-line) or 2 for single-phase, L is the one-way length and n is the number of parallel sets. DC model: VD = k · I · L · R / n (Chapter 9 Table 8, 75 °C).
    Table 9 values are for three single conductors in conduit at 60 Hz and 75 °C. Applying them to single-phase circuits is a common approximation.
    Ampacity: Table 310.16 × ambient correction (Table 310.15(B)(1)(1)) × adjustment for more than 3 current-carrying conductors (Table 310.15(C)(1)), not to exceed the terminal-temperature ampacity (310.15(A), 110.14(C)). Continuous loads: conductor ampacity of at least 125% of the load before correction (210.19(A)(1), 215.2(A)(1)).
    Values used per NFPA 70®, National Electrical Code® (NEC®), 2023 edition. The full code is available from NFPA, including free read-only online access. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association. ShaiLearning is not affiliated with or endorsed by NFPA.
    IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc. ShaiLearning is not affiliated with or endorsed by IEEE. IEEE standards are available from IEEE.
    Results are for educational and preliminary reference only. Always verify against applicable project standards, AHJ requirements, and licensed engineering judgment.
    See more resources: FE and PE Electrical Guide

    How to Use the Voltage Drop Calculator

    1. Choose the system. Pick three-phase, single-phase or DC.
    2. Enter the load. Give the current directly, or enter kW or kVA and the calculator works out the current. Enter the power factor for AC circuits.
    3. Enter the one-way length in feet or meters, plus your allowable drop (3% is the usual starting point) and the number of parallel sets.
    4. Pick the conductor and raceway. Choose copper or aluminum and PVC, aluminum or steel conduit. Switch to the DC-resistance model for DC circuits or quick estimates.
    5. Set ampacity conditions (optional). Open Ampacity conditions to set insulation and terminal ratings, ambient temperature, the number of current-carrying conductors and whether the load is continuous.
    6. Calculate. The result shows the recommended size, which limit governs, the voltage at the load, the maximum length at your limit, conductor losses and the other-material option. Open Show step-by-step solution for every substitution, or use Print / Save as PDF.

    Voltage Drop Formulas

    • AC (resistance and reactance): VD = k × I × L × (R cos θ + X sin θ) / n, with R and X in ohms per 1000 ft from NEC Chapter 9 Table 9 and L in thousands of feet
    • k = √3 for three-phase line-to-line drop, and k = 2 for single-phase and DC (out and back)
    • DC: VD = 2 × I × L × R / n, with R from Chapter 9 Table 8 at 75 °C
    • Percent drop: VD% = VD / V × 100
    • Maximum length at a limit: Lmax = (VD% / 100 × V) / (k × I × Ze / n)

    Here n is the number of parallel sets, L is the one-way length and Ze = R cos θ + X sin θ is the effective impedance. Using reactance matters on larger AC conductors, where X becomes a big share of the impedance.

    Worked Examples

    Three-phase: 480 V, 125 A, 250 ft, copper in PVC, 0.85 pf

    1. Ampacity first: 3 AWG copper at 75 °C is rated 100 A, too small for 125 A. 1 AWG at 130 A is the smallest that works.
    2. Table 9 for 1 AWG copper in PVC: R = 0.15 Ω/kft, X = 0.046 Ω/kft. Ze = 0.15 × 0.85 + 0.046 × 0.527 = 0.1517 Ω/kft.
    3. VD = √3 × 125 × 0.25 × 0.1517 = 8.21 V, or 1.71%.

    Here ampacity governs. Voltage drop alone would have allowed 3 AWG.

    Single-phase: 240 V, 40 A subpanel, 150 ft, 0.95 pf

    8 AWG copper carries 40 A but gives a 3.79% drop. 6 AWG gives 2.41% (5.78 V), so voltage drop governs and you upsize one step.

    FE/PE Exam and Field Tips

    • Use one-way length. The √3 or 2 in the formula already accounts for the return path. Doubling the length as well is a classic exam trap.
    • Check both limits. Size for ampacity, then check voltage drop, and take the larger conductor.
    • Steel conduit raises reactance. It makes the most difference on large conductors at low power factor.
    • Low-voltage DC needs care. A 1 V drop is only about 0.4% at 240 V, but about 2% at 48 V and 8% at 12 V.
    • Motor loads: size the branch circuit with the Motor Full-Load Current Calculator , then check the drop here.
    FAQ

    Frequently Asked Questions

    What voltage drop does the NEC allow?

    For most branch circuits and feeders, the NEC doesn't set a mandatory limit. Informational notes in 210.19 and 215.2 suggest about 3% for a branch circuit or feeder and 5% total to the farthest outlet, for reasonable efficiency and performance.

    Informational notes aren't enforceable requirements, but many engineers, specifications and some local codes treat them as design targets. Some equipment and articles set their own limits, so check those for your application.

    Should I enter one-way or round-trip length?

    Enter the one-way length from source to load. The formula multiplies by 2 for single-phase and DC, or by √3 for three-phase, to account for the return path.

    Why does the calculator use Chapter 9 Table 9 instead of Table 8?

    Table 8 gives DC resistance only. Table 9 gives AC resistance and reactance for conductors in PVC, aluminum and steel conduit, which is more accurate for AC circuits, especially 1/0 AWG and larger.

    Choose the DC-resistance model for DC systems, or when you want to compare with a simpler hand calculation.

    Does power factor affect voltage drop?

    Yes. In the AC model, effective impedance is R cos θ + X sin θ, so the share of drop caused by reactance changes with power factor. Table 9's printed effective Z assumes 0.85, but the calculator recomputes it for the power factor you enter.

    Why is my wire size larger than the ampacity table suggests?

    On long runs, voltage drop governs. The calculator tells you which limit set the size and what the other limit alone would allow, so you can see how much of the upsizing comes from length.

    How do ambient temperature and conductor bundling change the result?

    Ampacity from Table 310.16 is multiplied by an ambient correction factor (Table 310.15(B)(1)(1)) and, for more than three current-carrying conductors in a raceway, an adjustment factor (Table 310.15(C)(1)). The result also can't exceed the ampacity at the terminal temperature rating (110.14(C)).

    Can I use parallel conductors?

    Yes, for 1/0 AWG and larger (310.10(G)). Each set must match in length, material, size and insulation. Voltage drop divides by the number of sets, and ampacity multiplies by it.

    Is aluminum a good option?

    Often, for large feeders. Aluminum needs roughly one to two sizes larger than copper for the same ampacity and drop, but it usually costs less. The calculator shows the matching option in the other material with every result.

    Related Calculators

    Preparing for the FE or PE Electrical Exam?

    Get structured guidance from a licensed P.E. through the ShaiLearning FE & PE mentorship program. Join the waitlist, and explore the FE Electrical Guide and PE Power Guide.

    Values used per NFPA 70®, National Electrical Code® (NEC®), 2023 edition. The full code is available from NFPA, including free read-only online access. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association. ShaiLearning is not affiliated with or endorsed by NFPA.

    Results are for educational and preliminary reference only. Always verify against applicable project standards, AHJ requirements, and licensed engineering judgment.

    2 Responses

    1. Thanks Sr. Shaibu or Sharing this vital information on effective cable sizing, to ensure safety of life and to keep our reputation as professionals.

      But I want to suggest sir, for people like me that are just growing in this field, can you help to make the formula for calculating voltage drop and cable sizing in a formula way instead this one sir. I know some might understand that format, but I believe we learn things in different ways sir. Thanks so much once again sir.

    Leave a Reply

    Your email address will not be published. Required fields are marked *

    Related posts you might like

    Impedance Calculator

    This impedance calculator finds Z in rectangular and polar form from R and X, from |Z| and angle, from series

    Read More »

    Ohm’s Law Calculator

    The Ohm’s law calculator solves for voltage, current, resistance, and power from any two known values. Ohm’s law is the

    Read More »

    Why Large Power is Transmitted at High-Voltage

    Electricity is rarely made where it is used. A high voltage transmission system makes it possible to reach all demand

    Read More »